Free 3-Phase Current Calculator: kW to Amps

Calculate three-phase line current from real power, line-to-line voltage, and power factor. The same free tool also switches to single phase for loads supplied by one AC voltage.

Free complete single- and three-phase calculator — no account required

Current

Estimate line current from real power, voltage, phase, and power factor.

Load current
10.613 A
Apparent power
8.824 kVA
Formula
I = kW * 1000 / (sqrt(3) * VLL * PF)
Balanced-load formula

3-phase current calculator formula

I = (kW × 1,000) ÷ (√3 × VLL × PF)

To convert three-phase kW to amps, use total real power, line-to-line voltage, and power factor for a balanced load. The calculator handles the unit conversion and also supports single-phase estimates.

Worked comparison: 30 kW at 0.90 power factor

Holding power and power factor constant shows why the same load draws less current at a higher voltage.

Line voltageCalculationEstimated line current
208 V30,000 ÷ (1.732 × 208 × 0.90)92.5 A
240 V30,000 ÷ (1.732 × 240 × 0.90)80.2 A
480 V30,000 ÷ (1.732 × 480 × 0.90)40.1 A
Single-phase formula

Convert single-phase kW to current

I = (kW x 1,000) / (V x PF)

Use the voltage across the single-phase load. Power factor belongs in the denominator when the entered kW is real power. For a resistive unity-power-factor load, use 1.00.

Worked single-phase current examples

These examples show how voltage and power factor change current for common 120 V and 240 V loads.

LoadPower factorCalculationEstimated current
1 kW at 120 V1.001,000 / (120 x 1.00)8.33 A
2 kW at 120 V0.902,000 / (120 x 0.90)18.52 A
5 kW at 240 V0.905,000 / (240 x 0.90)23.15 A

Check the inputs before using the result

  • Use the load's line-to-line voltage for the balanced three-phase formula.
  • For single phase, use the actual voltage across the load and do not add the square-root-of-three factor.
  • Enter real power in kW and power factor as a decimal, such as 0.90 rather than 90.
  • Treat the result as a balanced steady-state estimate; starting, harmonic, and unbalanced loads need a different review.
  • Compare the estimate with equipment nameplate data and measured phase currents before acting on it.

From estimate to field-ready work

Use the free answer, then choose the depth you need

The calculator stays free for quick current estimates. Toolkit adds motor, transformer, voltage-drop, wire, and protection review tools. Pro Toolkit adds complete troubleshooting guides and browser-local field records with PDF output.

Need more than the free current estimate?

Toolkit is $5/month for advanced electrical tools. Pro Toolkit is $15/month and adds troubleshooting procedures, field records, and included library downloads. This current calculator stays free.

Compare $5 Toolkit and $15 Pro

Estimate boundary

This calculator estimates steady-state current from kW and power factor. Use equipment nameplate values and applicable motor, conductor, and protection requirements for final design decisions.