Modbus Register and REAL Workbench

Decode a register pair as REAL, DINT or DWORD with explicit byte order and zero-based addressing; review batch maps.

Worked example

Registers 0x3F80 and 0x0000 in ABCD order represent REAL 1.0 and unsigned integer 1065353216. A holding-register reference 40001 conventionally maps to protocol offset 0; confirm the device map.

IEEE754 REAL
1
Signed DINT
1,065,353,216
Unsigned DWORD
1,065,353,216
Combined hex
3F800000
Protocol offsets
0 / 1
Conventional holding-register references
40001 / 40002

ABCD means A high byte, A low byte, B high byte, B low byte. CDAB swaps words; BADC swaps bytes within words; DCBA swaps both. Modbus defines 16-bit registers; the device determines how multi-register data is represented.

Batch register-map review

First 100 rows shown. Overlapping register positions: 0. Review reused offsets.

Row 1: 0: REAL 1; DINT 1065353216; hex 3F800000

Row 2: 2: REAL 2; DINT 1073741824; hex 40000000

PLC data interpretation reference →
Requires Toolkit or Pro Toolkit

Modbus Register and REAL Workbench

Free preview

Inspect the worked example and fixed preview before choosing a plan.

Paid operation

Decode a register pair as REAL, DINT or DWORD with explicit byte order and zero-based addressing; review batch maps.

Unlocks with Toolkit or Pro Toolkit
  • Enter your own register pairs
  • Compare all four byte orders
  • Review a batch register map
Toolkit $5/mo · Pro Toolkit $15/mo

Toolkit unlocks advanced tool operation. Pro Toolkit adds the troubleshooting knowledge base, field-document builders, and included library downloads.

Compare plans and unlock

Your plan applies across the site. Work saved on this device is not synchronized to other devices.

Reference: Modbus protocol specifications. Review inputs and results against the exact device and site requirements.