Five-Point Analog Calibration Worksheet

Record as-found and as-left engineering readings against five signal points, calculate tolerance results and save a local job.

Worked example

For a 0–100 PSI range, 12 mA corresponds to 50 PSI. With a tolerance of 0.5% of span, the allowed error is ±0.5 PSI at every point. Select the tolerance basis required by the instrument and site.

PointAppliedExpectedAs foundError / resultAs leftError / result
0%4 mA0 PSI Untested Untested
25%8 mA25 PSI Untested Untested
50%12 mA50 PSI Untested Untested
75%16 mA75 PSI Untested Untested
100%20 mA100 PSI Untested Untested

Pass means the entered error is inside the selected tolerance only. It does not include reference-instrument uncertainty or establish traceability. Follow the approved calibration procedure.

Save and continue this job

Each save creates a separate version on this device. Saved work does not sync across devices. My Toolbox

Open the free analog scaling calculator →
Requires Pro Toolkit

Five-Point Analog Calibration Worksheet

Free preview

Inspect the worked example and fixed preview before choosing a plan.

Paid operation

Record as-found and as-left engineering readings against five signal points, calculate tolerance results and save a local job.

Unlocks with Pro Toolkit
  • Enter your own field observations
  • Save named local record versions
  • Export a watermarked PDF and editable backup
Toolkit $5/mo · Pro Toolkit $15/mo

This workspace requires Pro Toolkit. The standard Toolkit tier does not unlock it.

Compare plans and unlock

Your plan applies across the site. Work saved on this device is not synchronized to other devices.

Reference: Analog scaling formula and worked examples. Review inputs and results against the exact device and site requirements.

Five-Point Analog Calibration Worksheet | Automation Controls Toolbox